Jiangsu Acrel Electrical Manufacturing Co., Ltd.

Solid Core Current Transformer AKH-0.66/I 30I

● Measurement: Alternating Current (AC)

● Accuracy: Class 0.2/Class 0.5/Class 1.0

 Primary Current Input: 15~600A AC

● Application: On Busbar or Cable

● Rated Voltage: 660V AC

● Rated Frequency: 50~60Hz

● Installtion: Fixed by Sheet Metal/Fixed by Clutch Cover/35mm DIN Rail

 Loop Count of Cable: 1~5 Loops

● Standard&Certificate: IEC/EN61869-1;IEC/EN61869-2;CE


General

Current Transformer (CT) is used to transform the high AC current to small easily manageable values. They are connected with the panel meter or relay and they can help to measure the current or protect the equipment.

Overview AKH-0.66/I Series Solid Core Current Transformer (AKH-0.66/I 30I)

Dimension

Dimension.jpg

Model Name

Outline Size (mm)

Perforation Size (mm)

Installation Size (mm)

Tolerance (mm)

W

H

D

a

e

Φ

M

M

 
               

AKH-0.66/I 30I

 

60

78

36

31

11

23

34

57.5

±1

AKH-0.66/I 40I

75

95

45

42

11

31

40

57.5

AKH-0.66/I 60I

102

130

45

61.5

21

45

42

57.5

AKH-0.66/I 80I

118

140

45

82

11

52

60

57.5

Installation
pin1.jpgpin2.jpg
pin3.jpgpin4.jpg
pin5.jpg


Parameter
Model NameCurrent Ratio (A) (Primary/Secondary)Accuracy Class and Rated Load (VA)Loop Count of Cable Perforation Size(mm) /Pieces of Busbar
Class 0.2Class 0.5Class 1.0
 
 
 
 
 
AKH-0.66/I 30I 
 
 
 
 
 
 15/5(1)

1.5 
 
 /
 
 20/5(1)

1.5 
25~30/5(1)

1.5 
40~60/5(1) 

1.5 
 75~100/5(1)

1.5  
 
 
 30x10/1
 
 
 
 100/5(1)
1.5 
150~200/5(1) 
2.5 
250/5(1) 
3.75 
300~450/5(1) 

500/5(1) 
10 
600/5(1) 
10 
 
 
 
 
 
 
AKH-0.66/I 40I 
 
 
 
 
 
 
10/5(1) 

1.5 10  
 
 /
 
 
 
15/5(1) 

1.5 
20/5(1) 

1.5 
25~30/5(1) 

1.5 
40/5(1) 

1.5 
50~75/5(1) 

1.5 
100/5(1) 

1.5  
 
 
 40x10/1
 
 
 
150/5(1) 

2.5 
200/5(1) 
2.5 
250/5(1) 
3.75 
300~450/5(1) 

500~800/5(1) 
10 
1000/5(1) 10 

 
 
 
AKH-0.66/I 60I 
 
 
 
 
150/5(1) 

2.5  
 
60x10/1 

 60x6/1-2  
 
 
 
200/5(1) 
2.5 
250/5(1) 
3.75 
300~450/5(1) 

500~800/5(1) 
10 
1000~1250/5(1) 10 

1500~2000/5(1) 20 

2500/5(1) 30 

 
 
 
AKH-0.66/I 80I 
 
 
 
150/5(1) 

2.5  
 
 
80x10/1 
 
 
 
200~250/5(1) 
2.5 
300~450/5(1) 

500~800/5(1) 
10 
1000/1250/5(1) 10 

1500~2000/5(1) 20 

2500~3000/5(1) 30 



Get in touch with us!

Send us a message if you have any questions or request a quote. Our experts will give you a reply
within 24 hours and help you select the right products you want.

Hot Products
AKH-0.66/K-φ16 Split Core Current Transformer

AKH-0.66/K-φ16 Split Core Current Transformer

● AKH-0.66/K-Φseries split current transformers are mainly use... ● ···
AMC16-DETT Base Station DC Energy Meter For 5G Tower

AMC16-DETT Base Station DC Energy Meter For 5G Tower

● AMC16-DETT Base Station DC Energy Meter for 5G Tower is spec... ● ···
AHKC-EKA Open-loop Hall Effect Transducer (Split-core)

AHKC-EKA Open-loop Hall Effect Transducer (Split-core)

● Acrel AHKC series hall effect current sensor is mainly suita... ● ···
ADL3000-E or DTSD1352 Three-phase Multi-function DIN Rail Energy Meter

ADL3000-E or DTSD1352 Three-phase Multi-function DIN Rail Energy Meter

● ADL3000 is a smart meter designed for power supply system, i... ● ···